The charging performance of the valve controlled lead-acid battery is generally indicated by its charging characteristic curve, and the charging time depends on the depth of the discharge, the charging initial current and the ambient temperature. When the discharge depth is 50% and 100% (ie 50% Q. And 100% q.), The FM series lead-acid battery constant pressure ((2, 23V / monomer, 250c) and charging current flow value are The charging characteristics of I when I.
The charging current is decremented as the charge is increased, and the final current is extremely small, usually between 0.1 to 0.01, and the gas composite efficiency is close to 100%. At 25 degrees, the alkaline battery floating voltage is 2.23V. When the temperature of the monomer is changed, the floating voltage must be corrected, the temperature of the temperature is increased or the decrease of 5 degree voltage correction is reduced or increased by 15mV.